Technical features

Housing dimensions: 43 × 35 × 29mm (without terminals)

Bulb and capillary: stainless steel, with 150mm long PVC sleeve on the capillary. Capillary minimum bending radius is 5mm.

No capillary sleeve for temperature ranges above 400°C (750°F).

Temperature sensing element: oil filled bulb and capillary.

Caution: temperature ranges above 400°C (750°F) are filled with sodium-potassium eutectic. In case of breakage of the bulb or capillary, this liquid may self-ignite at room temperature in the presence of water or moisture.

Terminals: 6.35 × 0.8 quick connect terminals, 90° bended. Straight terminals or terminals with M4 screws also available on request. (MOQ apply).

Terminal positions and alignment allow the use of a connector with flat or bended terminals.

Adjustment: dia. 6mm shaft with 4.6mm flat, length 11.5mm. Other lengths, screw driver adjustment or fixed setting available on request.

Mounting: front bracket with 2 × M4 threads, 28mm distance.

Grounding: M4 thread on mounting bracket.

Contact: SPDT

Electrical rating, resistive loads:

- Open on temperature rise contact (C-1)

16A 250V, 50 ~60Hz: >100.000 cycles,

20A 250V, 50 ~60Hz: ≥ 50.000 cycles,

10A 400V, 50 ~60Hz: ≥ 50.000 cycles.

- Close on temperature rise contact (C-2): 6A 250V 50 ~60Hz: >100.000 cycles

Electrical rating, inductive loads:

- Open on temperature rise contact (C-1): 6A 250V, 50 ~60Hz: >100.000 cycles

- Close on temperature rise contact (C-2): 0.6A 250V 50 ~60Hz: >100.000 cycles